Siemens SIRIUS M200D Manual page 154

Industrial controls load feeders and motor starters
Hide thumbs Also See for SIRIUS M200D:
Table of Contents

Advertisement

Technical data
8.7 Switching frequency
Switching frequencies with deactivated soft start function (direct start)
Switching cycles/hour for 3RK1325-6LS71-.AA.(1.5 A to 12 A)
Mounting position
Rated current I
e
Ambient temperature
Motor protection
Class 5 (10a)
On time =30% (8 x Ie) / 0.1 s
On time =70% (8 x Ie) / 0.1 s
On time =30% (8 x I
) / 0.2 s
e
On time =70% (8 x I
) / 0.2 s
e
On time =30% (8 x I
) / 0.4 s
e
On time =70% (8 x I
) / 0.4 s
e
Class 10
On time =30% (8 x I
) / 0.1 s
e
On time =70% (8 x I
) / 0.1 s
e
On time =30% (8 x I
) / 0.2 s
e
On time =70% (8 x I
) / 0.2 s
e
On time =30% (8 x I
) / 0.4 s
e
On time =70 % (8 x I
) / 0.4 s
e
On time =30 % (8 x I
) / 0.8 s
e
On time =70 % (8 x I
) / 0.8 s
e
Duty cycle current rms value = 1.15 x I
1)
Duty cycle limit for motor starter. The motor should be protected against overload here by means of a thermistor.
2)
154
Vertical
2 A
2 A
40 °C
50 °C
1)
2)
1)
2)
600
3600 600
3600
360
2000 360
2000
300
2000 300
2000
180
1000 180
1000
150
1000 150
1000
90
520
90
520
600
3600 600
3600
360
2000 360
2000
300
2000 300
2000
180
1000 180
1000
150
1000 150
1000
90
500
90
500
75
490
75
490
45
250
45
250
→ motor protection
e
Horizontal
2 A
2 A
55 °C
40 °C
1)
2)
1)
2)
600
3600
600
3600
360
2000
360
2000
300
2000
300
2000
180
1000
180
1000
150
1000
150
1000
90
520
90
520
600
3600
600
3600
360
2000
360
2000
300
2000
300
2000
180
1000
180
1000
150
1000
150
1000
90
500
90
500
75
490
75
490
45
250
45
250
Manual, 08/2014, A5E02548958A/RS-AA/004
2 A
2 A
50 °C
55 °C
1)
2)
1)
2)
600
3600
600
3600
360
2000
360
2000
300
2000
300
2000
180
1000
180
1000
150
1000
150
1000
90
520
90
520
600
3600
600
3600
360
2000
360
2000
300
2000
300
2000
180
1000
180
1000
150
1000
150
1000
90
500
90
500
75
490
75
490
45
250
45
250
M200D AS-Interface Standard