3.14 Factory settings

Self-test error
If an error occurs, the "DEVICE" LED lights up red. The error can only be acknowledged by
switching the device off and then on again. If the error is still present, the self-test will return
an error again when the device is switched on. In this case, the motor starter will need to be
replaced.
Messages and actions
Self-test error
Switching element defective
Note
When diagnostics is carried out via the parameter channel (parameter echo), both messages
are combined to form the "Device error" message.
Note
Specific device components are monitored continuously (internally) by the motor starter and
the results signaled with the self-test messages. The message "Self-test error" may also
appear in the event of an internal monitoring error occurring, even if the self-test has not
been activated.
3.14
Factory settings
Description
The factory settings restore the settings of the motor starter as supplied, that is, the motor
model is deleted, faults are reset (if possible), and the operating hours counter is deleted,
etc.
This provides the option of resetting the motor starter in the event of incorrect
parameterization.
Note
Current maximum pointer and statistical data are not deleted.