Led Display Combinations - Siemens SIRIUS M200D Manual

Industrial controls load feeders and motor starters
Hide thumbs Also See for SIRIUS M200D:
Table of Contents

Advertisement

7.1.2

LED display combinations

You can detect certain faults/errors more accurately by looking at the combination of display
statuses.
Device status/mode
SF LED
Off
Off
Off
Off
Off
Off
Off
Off
Off
Device errors
Note
Acknowledging device errors
A device error can only be acknowledged by switching the power off and then on again.
If the error occurs again, however, the motor starter will need to be replaced.
SF LED
Red
Red
Red
M200D AS-Interface Standard
Manual, 08/2014, A5E02548958A/RS-AA/004
STATE LED
DEVICE LED
Green
Green
Off
Green
Flashing green
Green
Flashing green
Green
Flickering green
Green
Flashing yellow
Green
Flickering yellow Green
Off
Flickering red
Off
Flashing green
STATE LED
DEVICE LED
Red
Red
Off
Red
Off
Off
7.1 Diagnostics with LEDs
Device status/mode
Motor ON; no fault/error
Motor ON; no fault/error
Motor in soft startup; no fault/error
(sDSSte, sRSSte only)
Motor in soft run-down; no fault/error
(sDSSte, sRSSte only)
Motor ON; input controls
Manual mode connection abort without reset to
automatic mode
Tripping by means of input control function
(e.g. quick stop)
Self-test in progress (can only be called via
Motor Starter ES)
No startup parameters received
Device error
Current flowing with no ON command
(e.g.: contactor welded, thyristor fused)
Electronics defective, self-test error
No connection with AS-i
Diagnostics
135