Motor Starters - Siemens SIRIUS M200D Manual

Industrial controls load feeders and motor starters
Hide thumbs Also See for SIRIUS M200D:
Table of Contents

Advertisement

Technical data

8.2 Motor starters

Note
This product is designed for environment A (industrial environments). In household
environments, this device can cause unwanted radio interference. The user may be required
to implement appropriate measures in this case.
8.2
Motor starters
Motor starter version
Installation dimensions in mm
(in parentheses: with safety bars)
Weight (g)
Control circuit (AS-i interface)
Slave type
Suitable for AS-i master to spec.... (or higher)
AS-i slave profile IO.ID.ID2
ID1 code (factory setting)
Total power consumption from AS-i
without connected sensors
with connected sensors
Current consumption from U
Main circuit
Power of three-phase motors at 400 V
Rated operational current I
AC-1/2/3
AC-4
AC-53a (8 h operation)
Rated operational voltage
Certification to EN 60947-1 Appendix N
Certification to UL508 and CSA C22.2 No. 14
Product category according to UL
Motor ratings according to UL / CSA
3RK13.5- .K (2 A)
power (3ph /hp) / max. FLA
3RK13.5- .K (12 A)
power (3ph /hp) / max. FLA
144
Width
Height
Depth
at 24 V (without digital output)
AUX
C
e
At 400 V
At 500 V
At 400 V
At 400 V
for 460/480 V AC
for 575/600 V AC
for 230/240 V AC
for 460/480 V AC
DSte/RSte
294 (320)
215 (228)
159 (230)
2,880 g/3,130 g
A/B slave
AS-i Spec. 3.0 (M4)
7.A.E and 7.A.5
max. 100 mA
max. 300 mA
(total sensor current consumption <200mA)
Max. 155 mA
Typ. 75 mA
5.5 kW
12 A
9 A
4 A
400 V AC, 50/60 Hz
600 V AC, 50/60 Hz
NLDX
3/4 hp / 1.6 A
1 hp / 1.7 A
3 hp / 9.6 A
7.5 hp / 11 A
Manual, 08/2014, A5E02548958A/RS-AA/004
sDSSte/sRSSte
3,220 g/3,420 g
7
Max. 15 mA / 175 mA
Typ. 10 mA / 75 mA
5.5 kW
12 A (soft start)
9 A (direct start)
400 V AC, 50/60 Hz
480 V AC, 50/60 Hz
NMFT
3/4 hp / 1.6 A
2 hp / 6.8 A
5 hp / 7.6 A
M200D AS-Interface Standard