3.9.4
Data plausibility check
Description
The motor starter checks all incoming parameters to ensure that they are valid and plausible.
If parameters are incorrect:
● During a startup procedure (after Power ON), the messages "Group fault" and "Invalid
parameter value" are set.
The motor and the brake output remain switched off.
● During operation, the messages "Invalid parameter value" or "Parameter assignment not
possible in ON state" are set. "Group fault" is not set.
The motor and the brake output are not switched off.
Note
The parameter values that are currently valid are retained.
M200D AS-Interface Standard
Manual, 08/2014, A5E02548958A/RS-AA/004
Functions
3.9 Communication
73