Siemens SIRIUS M200D Manual page 38

Industrial controls load feeders and motor starters
Hide thumbs Also See for SIRIUS M200D:
Table of Contents

Advertisement

Functions
3.5 Motor control
Brake holding time on stopping
Note
Only active if an OFF switching command is present for the brake and the motor
simultaneously.
This device parameter causes delayed tripping of the brake output compared to the motor. It
also works in the event of a PLC failure.
During a reversing operation, the holding time and the lock-out time run concurrently.
Switching on in the opposite direction of rotation is not possible until the lock-out time has
expired. Switching on in the same direction is possible immediately in this case because the
lock-out time is aborted.
Priority rule
"Brake release delay on starting" takes priority over "brake holding time on stopping". An
expiring holding time is terminated if the release delay is restarted (by means of an ON
switching command for brake and motor.)
Settings
Brake release delay on starting
Brake holding time on stopping
Messages and actions
Brake output active
38
Device parameter
Message
Default setting
0 s
0 s
Brake coil is controlled, motor can be rotated.
Manual, 08/2014, A5E02548958A/RS-AA/004
Setting range
- 2.5 to + 2.5 s
Increment: 0.01 s
0 to 25 s
Increment: 0.01 s
Action
M200D AS-Interface Standard