Commissioning

6.1

Requirements

Parameter assignment
The motor starter parameters are assigned during startup using the AS-i Standard
procedure. Parameters can be modified and HMI (operator control and monitoring) tasks
performed during operation, either via the bus and the acyclic mechanism or locally via the
optical device interface.
The "Group diagnostics" parameter can be set to "block" or "enable". If "block" is selected,
no fault messages are sent.
A device error can only be acknowledged by switching the power off and then on again. If
the errors occur repeatedly, however, this indicates that the motor starter is defective.
Trip reset (Page 77) can be used to acknowledge all other errors.
Note
Please be sure to observe the voltage tolerance for the load voltage supply (contactors and
power electronics) up to 55 °C: 20.4 V to 28.8 V.
Rated operational current
The rated operational current for M200D motor starters is parameterized using the Motor
Starter ES software or the extended process image (Page 68).
Disconnecting the load from the supply system
You can set the integral disconnecting means to the OFF position to disconnect the motor
starter from the supply system.
NOTICE
Connecting/disconnecting a load during operation (that is, under load) is not permissible.
Reversing starter
Via the user program, make sure that before a change of direction takes place, the drive is
switched to "STOP" long enough to come to a standstill.
M200D AS-Interface Standard
Manual, 08/2014, A5E02548958A/RS-AA/004