Functions
3.7 System monitoring
Settings
Response to residual current detection
Response to current limit violation
Lower current limit
Upper current limit
Blocking current
(Motor Starter ES)
Blocking time
(Motor Starter ES)
Note
Individual parameters can only be set using Motor Starter ES.
Messages and actions
I
upper limit violation
e
I
lower limit violation
e
I
limit tripping
e
Residual current detected
Residual current tripping
Tripping due to motor blocking
50
Device parameter
Message
Default setting
Trip
Warning
18.75%
112.1%
800%
1 s
Dependent on parameterization
Trip (limit violation pending)
Dependent on parameterization
Trip (residual current detection)
Trip (blocking protection)
Manual, 08/2014, A5E02548958A/RS-AA/004
Setting range
Trip
Warning
Warning
Trip
18.75 to 100% of I
e
0% (= deactivated)
Increment: 3.125%
50 to 400% of I
e
0% (= deactivated)
Increment: 3.125%
150 to 1,000% of I
e
150 to 800% of I
e
(sDS..., sRS...)
Increment: 50%
1 to 5 s
Increment: 0.5 s
Action
-
M200D AS-Interface Standard