Settings
Response to overload - thermal
motor model
Trip class
Recovery time
Motor heating prewarning limit
Prewarning limit - remaining
time for tripping
(Motor Starter ES)
Idle time
(Motor Starter ES)
Cannot be parameterized for soft starters with startup mode = direct
1)
Note
Individual parameters can only be set using Motor Starter ES.
M200D AS-Interface Standard
Manual, 08/2014, A5E02548958A/RS-AA/004
Device parameter
Default setting
Trip without restart
CLASS 10
90 s
0% (= deactivated)
0 s (= deactivated)
0 s (= deactivated)
3.6 Motor protection
Setting range
Trip without restart
Trip with restart
Warning
CLASS 5 (10a)
CLASS 10
CLASS 15
1)
CLASS 20
1)
CLASS OFF
60 to 1,800 s
Increment: 30 s
0 to 95%
Increment: 5%
0 to 500 s
Increment: 1 s
0 to 255 s
Increment: 1 s
Functions
43