Appendix
A.2 Data formats and data sets
A.2.2.1

Writing data set 93 (commands)

Byte.Bit
0
1
2
3
4
5
6
7
8
9
Data is transferred to the device using the "Write data set" function.
The following commands are used:
Object name
Object length
Value range
Meaning
172
Code
Meaning
0x21
0x00
0x00
0x00
(1 byte)
0x00
Do not process any commands
0x01
Process command_1
0x02
Process command_1 and 2
0x03
Process command_1, 2, and 3
0x04
Process command_1, 2, 3, and 4
0x05
Process command_1, 2, 3, 4, and 5
See below
Command_1
Command_2
Command_3
Command_4
Command_5
Code
Command
1 byte
0 to 255
0
1
2
3
6
7
9
10
11
13
14
15
16
Meaning
No function
Trip reset
Emergency start ON
Emergency start OFF
Factory settings
Delete maximum pointer
Restart
Parameters disabled CPU/master ON
Parameters disabled CPU/master OFF
Delete logbook - Triggering operations
Delete logbook - Events
Cold run ON
Cold run OFF