● In the M200D AS-i Standard motor starter, the rated operational current is preset at the
factory to the maximum value. (For testing at startup without fieldbus and without
previous parameterization)
Note
If the parameter bits of slave 1 are not changed during AS-i parameter assignment and
no parameters are sent to the starter via process image or data set, the motor current is
set to the highest value. This means that there may not be any overload protection.
● In the "Motor Starter ES" software, the rated operational current is preset to the minimum
value for safety reasons. You must therefore parameterize this value when you configure
the system Otherwise the motor starter would trip when it starts for the first time due to
overloading.
● The rated operational current depends on the "startup mode" parameter on motor starters
with soft starter function. If the startup mode is set as "direct", the choice of rated
operational current is restricted to 9 A.
Settings
Rated operational current
On soft starters (sDSSte, sRSSte) in "direct" startup mode
1)
Note
The setting range depends on the device type!
26
Device parameter
Default setting
In the motor starter: Maximum value
In Motor Starter ES: Minimum value
Setting range
0.15 A to 2.0 A
1.5 A to 9.0 A
1.5 A to 12.0 A
Increment: 10 mA
M200D AS-Interface Standard
Manual, 08/2014, A5E02548958A/RS-AA/004