Mounting/Connecting
4.2 Connecting
4.2.5

Power terminal

Wiring X1 (power supply) and X2 (motor connection)
The supply voltage is fed via power connector X1.
The motor is supplied via power connector X2.
Note
When inserting the pin/female contact insert into the connector housing, make sure that the
coding is positioned correctly.
Connector monitoring
1)
Temperature sensor
2)
100
Pin
Connector
Socket X2
X1
without
brake
1
Phase L1
L1 out
2
Phase L2
---
3
Phase L3
L3 out
4
N
---
5
---
2)
6
---
---
7
---
L2 out
8
---
2)
11
---
1)
12
---
1)
PE
PE
Socket X2
with 400 V /
with 180 V DC
230 V AC brake
L1 out
L1 out
N (for 230 V AC
---
brake)
L3 out
L3 out
Brake L1
Brake L1
(switched)
(switched) "-"
2)
2)
Brake L3
Brake L3
(direct, for
(direct) "+"
400 V AC
brake)
L2 out
L2 out
2)
2)
---
---
---
---
PE
PE
M200D AS-Interface Standard
Manual, 08/2014, A5E02548958A/RS-AA/004