Configuring/assigning parameters
5.5 Process data and process image
Extended cyclic process image of inputs (PII)
With M200D AS-i Standard starters, Slave 1 returns diagnostics data, messages, and
measured values to the master or CPU on a continuous (cyclical) basis. This involves
4 bytes of data. These 4 bytes can be accessed from the user program in the same way as
analog data is accessed. Transfer from the starter (slave) to the master takes place serially
via the CTT2 protocol.
In this case, the extended cyclic process image of inputs can also be read out if it has not
been activated during configuration (P1 = 1).
Please refer to the documentation for the AS-i master for detailed information on analog data
transfer.
Extended process image (PII) from starter
Byte/bit pos.
Coding
Transmit data
Addr.+ 0
0.0...7
Unsign. 8
Addr.+1
1.0...6
Unsign. 6
1.7
Bit 1
Addr.+2
2.0
Bit 1
2.1
Bit 1
2.2
Bit 1
2.3
Bit 1
2.4
Bit 1
2.5
Bit 1
2.6
Bit 1
2.7
Bit 1
Addr.+3
3.0
Bit 1
3.1
Bit 1
3.2
Bit 1
3.3
Bit 1
3.4
Bit 1
3.5
Bit 1
3.6
Bit 1
3.7
Bit 1
Reference
For more information about system integration and data management in the controller, refer
to the "AS-Interface system" System Manual.
124
Meaning
Motor current I
(%)
max
Motor heating (%)
Asymmetry >= 40%
Ready (automatic)
Motor CW
Motor CCW
Group fault
Group warning
Temperature sensor overload
Thermal motor model overload
Sensor supply overload
Residual current detected
Asymmetry detected
Circuit breaker open/tripped
Connector removed on line side
Manual mode local
Invalid parameter value
Free
Free
0 to 255 [x 3.125%]
0 to 100 [x 2%]
1 = Active
1 = Active
1 = Active
M200D AS-Interface Standard
Manual, 08/2014, A5E02548958A/RS-AA/004