5.5.2

Extended cyclic process image via CTT2

Extended cyclic process image of outputs (PIO)
With M200D AS-i Standard motor starters, parameters are transferred from Slave 1 to the
master on a continuous (cyclical) basis. This involves 4 bytes of data. These 4 bytes can be
accessed from the user program in the same way as analog data is accessed.
Transfer from the master to the motor starter (slave) takes place serially via the CTT2
(Combined Transaction Type 2) protocol.
The parameters in the extended cyclic process image can only be used if the extended cyclic
process image has been activated in the configuration (P1=0)
Please refer to the documentation for the AS-i master for detailed information on analog data
transfer.
Extended process image (PIO) to starter
Byte/bit pos.
Coding
Addr.+ 0
Addr.+1
Unsign. 16
Addr.+2
2.0
Bit 1
2.1...2
Bit 2
2.3...4
Bit 2
2.5...6
Bit 2
2.7
Bit 1
Addr.+3
3.0
Bit 1
3.1...2
Bit 2
3.3
Bit 1
3.4
3.5...6
Bit 2
3.7
M200D AS-Interface Standard
Manual, 08/2014, A5E02548958A/RS-AA/004
Meaning
Rated operational current I
Group diagnostics
Response to overload - thermal motor
model
Temperature sensor
Response to temperature sensor
overload
Response to residual current detection
Response to asymmetry
Response to
circuit breaker OFF
Connector monitoring
Reserved
Response when infeed connector
removed
Reserved
Configuring/assigning parameters
5.5 Process data and process image
15 to 200 [x 10 mA] (0.15 to 2 A)
e
150 to 1,200 [x 10 mA] (1.5 to 12 A)
[0]: block
[1]: Enable
[0]: Trip without restart
[1]: Trip with restart
[2]: Warning
[0]: Deactivated
[1]: Thermoclick
[2]: PTC type A
[0]: Trip without restart
[1]: Trip with restart
[2]: Warning
0]: Warning
[1]: Trip
0]: Warning
[1]: Trip
[0]: Group fault
[1]: Group fault only after ON command
[2]: Group warning
0]: Deactivated
[1]: Line side
[0]: Group fault
[1]: Group fault only after ON command
[2]: Group warning