Digital Output Out1 (A Coding) - Siemens SIRIUS M200D Manual

Industrial controls load feeders and motor starters
Hide thumbs Also See for SIRIUS M200D:
Table of Contents

Advertisement

Pin assignment
The following diagrams show examples of circuits (2 and 3-wire system):
Note
The supply voltage for the digital inputs is short-circuit proof. The current is limited to max.
200 mA. If a short-circuit or overload situation occurs in the sensor supply, the switching
element (motor) and brake output are shut down and a group fault is output. You must
acknowledge this fault with a trip reset.
4.2.7.2

Digital output OUT1 (A coding)

The motor starter is equipped with a digital output, which you can connect directly to an
actuator. The output is active when a group fault is present.
The output can be loaded to max. 0.5 A and protected electronically against short-circuits.
A connector (M12, 4 or 5-pin, A-coded) is used for establishing the connection. The motor
starter is equipped with a range of sockets.
M200D AS-Interface Standard
Manual, 08/2014, A5E02548958A/RS-AA/004
2-wire system
Example: Connecting the digital output
3-wire system
Mounting/Connecting
4.2 Connecting
105