3.19.1.2

BICO technology for SIMADYN D

DANGER
!
NOTE
Data types for
technological
connectors
D7-SYS connection data type in CFC
Data type of the technological
connector in the parameter description
Configuring
technological
connectors
System- and communication configuring D7-SYS - SIMADYN D
Edition 12.2003
With MASTERDRIVES operator control devices, with BICO technology
you can change interconnections between blocks. You can change
configured software without using the CFC. You can change
interconnections on a T400 technology board, Application module
FM 458 or CPU module in a SIMADYN D subrack.
• BICO technology and the CFC test mode should not be used
simultaneously.
• If you make online changes in the CFC test mode, then you
must first re-compile before you use BICO technology.
Changes made in the CFC only become effective on the display
of the operator control device after compilation.
• If changes were made using BICO technology without saving
them in the CPU change memory, then data consistency
between the changes on the CPU and your configured software
on the PC/PG are no longer guaranteed, and can no longer be
established by updating the project. If you wish to avoid this
inconsistent condition, you must first RESET the module
before you use CFC in the test mode
If you have made interconnection changes using BICO technology, and
then you activate the CFC test mode, a warning is displayed in the form
of the "different software release" dialog box.
You can configure the following D7-SYS connection data types of the
blocks as technological connectors:
Bool
Integer
O2
I2
In order that you can change interconnections between blocks using
BICO technology, you must, in addition to the parameters, still configure
technological connectors at block outputs in the CFC. You can use block
outputs with technological connectors to change the interconnection
using BICO technology.
Technological connectors are configured as follows:
Designate the block output with a pseudo comment @TC_nnnn, with
nnnn: four-digit technological connector number 0000 to 9999
Communications configuring
Double
Word
Real
Integer
I4
V2
I4
SDTime
I4