Csp, Current Setpoint Calculation - Siemens SIMADYN D Manual

System- and communication configuring
Hide thumbs Also See for SIMADYN D:
Table of Contents

Advertisement

Closed-loop thyristor current control
CAV.
YFI
Frequency [kHz] of the V/f conversion of the current actual value
(uncorrected value)
YFO
Offset actual value [kHz]
YFO =
When the closed-loop thyristor current control is switched-out
(I=0), the frequency at YFO corresponds to the offset error of the
V/f converter in the Sitor. The output only indicates values up to
10% of the system current.
YAU
Limit of the current-dependent inverter stability limit [ ° ]
Interdependencies: Value > 0, if XF2 > 0
TCC
Internal measuring time of the current actual value conversion
[ms]
ACO
Handshake for PC6 block
QSF
Fault
Table 5-7
I/O CAV

5.2.5 CSP, current setpoint calculation

Hardware address
Current setpoint (with sign)
Pos. I_max (abs. value)
Neg. I_max (abs. value)
Gradient, setpoint smoothing
Gradient, integrator inhibit
Fig. 5-16
CSP represented in the CFC
Setpoint
smoothing
5-34
Significance
YFI
-
60[kHz]
-
XFO
is used, in conjunction:
CSP
GV
AD
R
WC
R
WCU
R
WCL
R
GLI
R
IL
Enable
BO
EN
The current setpoint (SOL.YWC) is limited to the absolute value of the
current limits CSP.WCU and CSP.WCL.
To smooth the setpoint, the difference between setpoint CSP.WC and the
CSP.YCW current setpoint, output in the previous cycle, is formed and is
output at CSP.YE.
The difference, compared with parameter GLI, decides the change of
output YCW
If the difference > GLI, then the value of GLI is output.
If the difference < GLI, but, > GLI/2, this is limited to GLI/2.
If the difference <GLI/2, this is transferred without any correction.
The result is added to output YCW with the correct sign.
The absolute value of the smoothed and limited current setpoint is output
at CSP.YCW.
YCW
R
Current setpoint, smoothed (abs. value)
YE
R
New-old difference (with sign)
QCL
BO
Current limit reached
QIU
BO
Pos. inhibit, integrator
QIL
BO
Neg. inhibit, integrator
ZVA
INT
Diag.:Status
System- and communication configuring D7-SYS - SIMADYN D
Value\connection
(Default: 0.0)
(Default: 0.0)
(Default: 0.0)
CAV.YAU → CPI.CLU
→ PC6.AWS
(Default: 0 ms)
CAV.ACO → PC6.ACI
(Default: 0)
CAV.QSF → SOL.QSC
(Default: 16#0000)
Edition 06.2002

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

D7-sys

Table of Contents