Siemens SIMADYN D Manual page 341

System- and communication configuring
Hide thumbs Also See for SIMADYN D:
Table of Contents

Advertisement

Communications configuring
Structure of the 1st
line
Character of the 1st
Significance
line
1-24
Date/time
25-27
Text: "P:"
28-32
Prefix
33-35
Text: "S:"
36-40
Suffix
41-45
Text: "Type:"
46
Message type
('C','F','W' or 'S')
47-50
Text: "Nr:"
51-53
Sequence number
54
Text: " "
55-67
Measured value
(optional: this is only
entered if the
message contains a
measured value)
68
Blanks (optional)
69-76
Measured value unit
(optional: is only
entered if the
message contains a
measured value)
77, 78
Special characters,
CR and LF
Table 3-83
Structure of the MSPRI evaluation block message, 1st line
Structure of the
2nd line
3-252
Contrary to the message evaluation block MSI, the format of the
messages of the MSPRI evaluation block can be freely selected. Here,
only one format is output. Thus, there are no connections to select a
format when configuring the block. The MSPRI block has been especially
developed to output messages on a printer. All of the messages are
output as text and with line feed. A message consists of a maximum of
two lines.
Output format
Day.Month.Year, Hour:Minute:Second:Millisecond
Max. 5 characters and right justified
Max. 5 characters and right justified
One character
Max. 3 characters and right justified
Is output as floating value in the following sequence:
sign (positive = "+", negative = "-")
number of places before the decimal point followed by a
decimal point and 6 places after the decimal point
exponent, started with the character 'e'
sign (positive = "+", negative = "-") as well as 2 exponent
positions
8 characters
Line feed
System- and communication configuring D7-SYS - SIMADYN D
Edition 12.2003