Communications configuring
Function blocks
3-68
• A maximum of one transmitter- and/or one receiver block per
communications partner
• Permitted communication utilities:
− process data
− parameter processing of variable-speed drives
• Permitted data transfer mode: Refresh (for receivers, also multiple)
• A maximum of one synchronization function block SYNPRO per SS52
communications module
• A maximum of one diagnostics function block DIAPRO per SS52
communication module
Central block PROFIBUS DP coupling @CSPRO
CS7 module name.connector
PROFIBUS address
Baud rate
Only slave functionality
Host CPU monitoring time
Fig. 3-20
Central block, PROFIBUS DP coupling @CSPRO
• Use
This function block initializes and monitors the PROFIBUS DP
coupling (CS7 with SS52). It may only be configured in a sampling
time of 32 ms ≤ TA ≤ 255 ms.
• I/O
ECL, ECO, CDM, QTS and YTS are service- and diagnostics I/O
which are generally used for SIMADYN D start-up (commissioning).
They are not used for configuring.
Further information
on the I/O of the central block PROFIBUS DP coupling @CSPRO,
refer to the User Documentation "SIMADYN D, function block library".
@CSPRO
GV
-
CTS
ECL
-
I
MAA
ECO
BDR
CDM
I
-
QTS
SLA
I
-
I
LCC
-
System- and communication configuring D7-SYS - SIMADYN D
I
-
Error class
I
-
Error code
BO
-
Coupling status
BO
-
Block status
Edition 12.2003