Enocean Rf Networks; Technology - Siemens Desigo TRA Engineering, Mounting And Installation Manual

Hide thumbs Also See for Desigo TRA:
Table of Contents

Advertisement

Summary of EnOcean RF standards (http://www.enocean-alliance.org/en/enocean_standard/)
High reliability
Low energy demand.
66 / 84
Siemens
Building Technologies
14

EnOcean RF networks

14.1

Technology

(This section is based on the document "EnOcean Range planning" by Engineer
Armin Anders, EnOcean LLC).
The patented EnOcean RF technology creates a surprisingly far-reaching signal
with remarkably little energy. So that devices can be operated trouble-free without
solar cells, Piezo elements or thermocouples.
The patented EnOcean RF technology creates a surprisingly far-reaching signal
with remarkably little energy. So that devices can be operated trouble-free without
solar cells (for room temperature sensors) or Piezo elements (switches/buttons).
At just 50 µWs, a standard EnOcean RF modules can transmit a signal over a
distance of 300 m / 1000 ft (in a free field). The secret is the signal duration is just
one one thousandth of a second and triggers, executes and concludes the entire
process.
Figure: EnOcean technology uses
License-free frequency ranges 868 MHz or 315MHz at 1% duty cycle
(comply with local law/releases).
Multiple telegram transmission with checksum.
Short telegrams (ca. 1ms) results in a low probability of collisions.
High range: 30 m / 100 ft in buildings & 300 m / 1000 ft unhindered.
Repeater available for extensions.
Uni and bidirectional communications.
High data transmission rate of 125 kbps.
Low "data overhead".
ASK modulation.
Desigo TRA Engineering, mounting and installation
EnOcean RF networks
CM111043en_09
2016-02-22