Number Of Coupling Modules In A Subrack; Reorganizing A Data Interface - Siemens SIMADYN D Manual

System- and communication configuring
Hide thumbs Also See for SIMADYN D:
Table of Contents

Advertisement

Communications configuring
6.octet
0000 xxxx xxxx xxxx
Significance 2
Fig. 3-7
Time and date
3.1.4.4

Number of coupling modules in a subrack

Overview
Assigned address
space
3.1.4.5

Reorganizing a data interface

General
3-20
− 3rd octet to 6th octet:
Specify the time between 00:00 and 24:00.
Resolution = 1ms
0 ms≤x≤86400000 ms
The first 4 bits are not assigned in the sixth octet
3.octet
xxxx xxxx xxxx xxxx dddd dddd dddd dddd
27
The number of CS coupling modules (CSH11, CS12/13/14, CS22 and
CS7) are restricted by two system limits:
• subrack size
The largest subrack in the SIMADYN D system has 24 slots. As a
subrack must have at least one CPU, theoretically, 23 slots remain.
• available address space
In practice, these limits are seldomly reached. For CS modules, the L-
and C bus each have 1 Mbyte address space.
The individual CS modules always occupy a constant address space on
the backplane bus.
• Example
CS7 always occupies 64 Kbyte on the L bus, independent of how
many modules are configured.
Module type
CS12/13/14, CS22
CSH11
CS7
Table 3-16
Occupied address space
A data interface can be re-formatted without having to interrupt the RUN
condition or diminish performance.
2.octet
1.octet
15
Significance 2
00
Significance 2
Backplane bus
C bus
C bus
L bus
System- and communication configuring D7-SYS - SIMADYN D
00
Significance 2
Occupied address space
128 Kbyte
64 Kbyte
64 Kbyte
Edition 12.2003