Communications configuring
3.17.4.3

Parameterizing the MASTERDRIVES MC

Fig. 3-67
Parameters for MASTERDRIVES MC (DriveMonitor, and SIMOVIS)
3-172
The following parameters must be set in the SIMOVERT
MASTERDRIVES MC (refer to the User Documentation
„MASTERDRIVES MC"):
Parameter
P740
Own node address, transceiver/slaves: 1...200 (dispatcher=0)
Telegram failure time, if the telegram fails, fault F056 is output.
P741
The usual values: > 3 x bus cycle time (refer to P746)
P742
Send power, dependent on the length of the fiber-optic cable
P743
Number of nodes in the SIMOLINK ring
P745
Number of channels (this is only relevant for the dispatcher)
P746
Bus cycle time (only relevant for the dispatcher)
P749
Read address, which is generated from the node address and
the channel number, whereby the node address does not have
to match its own node address (P740)
Example: 2.0 = node address 2, channel number 0
P751
Send data,
Index 1 = channel 1 (low word),
Index 2 = channel 1 (high word),
Index 3 = channel 2 (low word),
etc.
SIMOLINK configuration
P755
0x100 should be entered for modes 4 and 5 so that
synchronization is realized (this is valid from firmware release
1.4 for MASTERDRIVES MC)
Table 3-63
Parameters for MASTERDRIVES MC
Significance/setting
System- and communication configuring D7-SYS - SIMADYN D
Edition 12.2003