I/O
CPI.
AD
Hardware address
WC
Current setpoint (absolute value)
CPC
Pre-control angle in the discontinuous range
XC
Current actual value (with sign)
CLU
Limit of the current-dependent inverter stability limit [ ° ],
if this function is not required, CLU=ALU should be set to 150 [°].
ALU
Inverter control limit of the firing angle [ ° ]
the minimum of CLU and ALU is used
ALL
Rectifier control limit of the firing angle [ ° ]
SV
Setting value for torque reversal or continuous tracking
(only active for S = 1)
(SV corresponds to the torque reversal of the motor EMF)
ILU
Integrator inhibit, positive direction
ILL
Integrator inhibit, negative direction
S
Sets the integrator with the value SV
SVC
Mode: Pre-control of the CPI
KP
Proportional gain [1]
TN
Integral action time [ms]
PC
Inhibits integrator component
(with PC=1 ⇒ integrator is deleted)
EN
Controller enable
(with EN=0, all Yxx are immediately set to zero)

Y
Firing angle [ASG]
YE
System deviation
YWP
Pre-control angle [ASG]
YP
P component
YI
I component
QU
Controller at its positive limit (M1)
QL
Controller at its negative limit (M2)
TA
Sampling time: Current controller (configured)
YW
Firing angle [ ° ]
(same as Y, only in another format)
ZSU
Inverter control limit, effective [ ° ]
(internally used limit f (ALU,CLU) is displayed)
ZSL
Rectifier control limit, effective [ ° ]
(ALL limit is displayed)
Table 5-11
I/O CPI
System- and communication configuring D7-SYS - SIMADYN D
Edition 06.2002
Significance
=
YE
WC
XC
Closed-loop thyristor current control
Value\connection
CSP.YCW → CPI.WC
CPC.Y → CPI.CPC
(Default: -0.333333
= 30[ASG] )
CAV.YC → CPI.XC
CAV.YAU → CPI.CLU
(Default: 150.0)
(Initialization connection/
default: 150.0)
(Initialization connection/
default: 30.0)
SOL.YSV → CPI.SV
{>-1 ... +1<}
CSP.QIU → CPI.ILU
(Default: 0)
CSP.QIL → CPI.ILL
(Default: 0)
SOL.QCS → CPI.S
(Default: 0)
(Default: 0.01)
(Default: 10000 ms)
(Default: 0)
SOL.QCE → CPI.EN
CPI.Y → PC6.WAS
(Default: 0.0)
(Default: 0.0)
(Default: 0.0)
(Default: 0.0)
(Default: 0.0)
(Default: 0)
(Default: 0)
(Default: 0 ms)
(Default: 0.0)
(Default: 0.0)
(Default: 0.0)
5-41