Siemens SIMADYN D Manual page 469

System- and communication configuring
Hide thumbs Also See for SIMADYN D:
Table of Contents

Advertisement

Significance of
fault bits YW2, with
HM2 → YF2
YW2→YF2
Bit 1
Hardware fault of the current actual value sensing (Sitor)
ITDC: Current actual value has not been latched (saved).
Cause: V/f conversion frequency not present
check the current actual value sensing (60 kHz) or ITDC
Bit 2
Overcurrent M1
check the system values, connector CAV.CX1 and
initialization connections CAV: RRC, ARC, NF, XFO, AL1
Bit 3
Overcurrent M2
check the system values, connector CAV.CX2 and
initialization connections CAV: RRC, ARC, NF, XFO, AL2
Bit 4
CAV configuring error
check the initialization connections, CAV:
RRC, ARC, AL1, AL2, IAV, XF2, NF, XFO
Bit 5
Hardware fault: Voltage actual value sensing (Sitor)
ITDC: Voltage actual value has not been latched (saved).
Cause: V/f conversion frequency not present
check the voltage actual value sensing (60kHz) or ITDC
Bit 6
EMF configuring error
check the initialization connections EMF: RRV, ARV, AAV, XFO
Bit 7
Pulse position error (PC6)
Cause: Erroneous pulse position
check the line supply values and connectors PC6: DIL, DIZ
Bit 8
Configuring error
→ AAV voltage specified too high (1.35*AAV > 2*ARU)
Fault, zero current signal for M1 ⇔ M2
Bit 9
check the zero current signal from the SITOR interface
(only with NZM=0)
Bit 10
SOL configuring error
check the initialization connections SOL: TH0, TCP
Bit 11
SOL block, internal status fault
check the ITDC hardware
Bit 12
FCS configuring error
check the initialization connections FCS: RRC, ARC and FC
Bit 13
PA6 configuring error
check the initialization connections PA6: NAZ, NEP, NWD, INV, FNT
Bit 14
configuring error
PC6
→ check the initialization connections
Bit15-16
Logical 0
Table 5-6
Fault list SOL.YW2 .YF2
System- and communication configuring D7-SYS - SIMADYN D
Edition 06.2002
Fault message → remedy
(NZM=0, Sitor) or Iact >3%
PC6: LDU, LDL, AWS, DAG, DAW
Closed-loop thyristor current control
Source
CAV
CAV
CAV
CAV
EMF
EMF
PC6
SOL
SOL
SOL
FCS
PA6
PC6
5-29

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

D7-sys

Table of Contents