Siemens SIMADYN D Manual page 464

System- and communication configuring
Hide thumbs Also See for SIMADYN D:
Table of Contents

Advertisement

Closed-loop thyristor current control
SOL.
Significance
ZST
Diag.: Stop in the status of the specified number (ZVA)
(The pre-set value (Default value) can only be modified by
trained personnel!)
TA
Processing time, switch-over logic stage
QON
Closed-loop current control operational
(only enabled if there are no faults and after a switch-on
command and setpoints WC1+WC2 > WCL > 0.0)
QPL
Pulse inhibit
(the status is displayed at connector ITDC-X5:15 = 0)
QPS
Shift to inverter operation is executed
(The firing angle PC6.AWS becomes active.)
QCE
Enables the current controller
QCS
Sets the current controller FB-CPI, set or track
Q01
Torque direction M1 operational
(setpoint is switched-through to YWC)
Q02
Torque direction M2 operational
(setpoint is switched-through to YWC)
QSE
Test mode is switched-in
QM0
M0 requested, current setpoint < WCL
= neither M1 nor M2 requested
QM1
M1 requested
QM2
M2 requested
QCC
Control word for FB-PC6
YWC
Current setpoint
YSV
Setting value, current controller even when tracking is switched-
in
ZVL
Diag.:(n-1) status
ZVA
Diag.:(n) status , control state machine
ZVN
Diag.:(n+1) status
ZIA
Diag.:Status, interrupt state machine
YHW
Signaling word hardware ITDC
(masked by HMH)
YW1
Alarm word 1
YW2
Alarm word 2
QW
Sum, alarm
1 bit in YW1 or YW2 = 1
YF1
Fault word 1
YF2
Fault word 2
QF
Sum, fault signal
1 bit in YF1 or YF2 = 1
Table 5-3
I/O SOL
5-24
(masked using HM1)
(masked using HM2)
System- and communication configuring D7-SYS - SIMADYN D
Value\connection
(Default: 100 )
(Default: 0 ms)
(Default: 0)
(Default: 0)
(Default: 0)
SOL.QCE → CSP.EN
(Default: 0)
SOL.QCS → CPI.S
SOL.QCS → CSP.EN
(Default: 0)
SOL.Q01 → CAV.IM1
(Default: 0)
SOL.Q02 → CAV.IM2
(Default: 0)
(Default: 0)
(Default: 0)
(Default: 0)
(Default: 0)
SOL.QCC → PC6.ICC
(Default: 16#0000)
SOL.YWC → CSP.WC
(Default: 0.0)
SOL.YSV → CPI.SV (Default:
0.0)
(Default: 0)
(Default: 0)
(Default: 0)
(Default: 0)
(Default: 16#0000)
(Default: 16#0000)
(Default: 16#0000)
(Default: 0)
(Default: 16#0000)
(Default: 16#0000)
(Default: 0)