Appendix; Standard Configuration Of Parameters - Siemens SIMADYN D Manual

System- and communication configuring
Hide thumbs Also See for SIMADYN D:
Table of Contents

Advertisement

5.8

Appendix

5.8.1 Standard configuration of parameters

Connec-
tion
PA6.SYX
Mode: Source, synchronizing voltage
PA6.XDA
Offset angle
PA6.NAZ
No. of failed line supply periods
Condition: 0 ≤ NAZ ≤ 3050,
PA6.NEP
No. of line supply periods
Condition: 0 ≤ NEP ≤ 5000,
PA6.NCM
Mode : Line supply handling
PA6.FAM
For NCM=1: Refer to 4
For NCM=2: Average value generation
For NCM=3: Decrease phase difference { ≥ 1 ...≤ 1000 }
For NCM=4: Decrease phase step { ≥ 1 ...≤ 1000 }
PA6.INV
Mode for rotating field detection
PA6.FNT
Line frequency [Hz] for start of synchronization
Condition: 6 ≤ FNT ≤ 600, > QSF\bit 9 = 1
Connec-
tion
EMF.RRV
Rated Sitor voltage of the sensing [V].
Condition: RRV ≥ ARV,
EMF.ARV
Rated system / motor voltage [V]
Condition: RRV ≥ ARV
EMF.NF
Normalization of the voltage actual value at YUA
EMF.AAV
Line supply voltage [V].
Condition:
AAV
EMF.XFO
Offset frequency of the V/f converter [kHz]
Condition: -6 kHz ≤ XFO ≤ 6 kHz,
EMF.RA
Normalized armature resistance
EMF.TA
Armature time constant [ms]
EMF.T
Smoothing time for YEV value
(the smoothing is switched-out with T=0)
System- and communication configuring D7-SYS - SIMADYN D
Edition 06.2002
Significance
{ -180° ... +180° }
> QSF\bit 9 = 1
> QSF\bit 9 = 1
Significance
> QSF\bit 14 = 1
0,
> QSF\bit 14 = 1
π
2
⋅ ≥
,
>QSF\bit 14 = 1
ARV
3
> QSF\bit 14 = 1
Closed-loop thyristor current control
Value
0
0.0
8
5
{ 0 ... 4 , >4= 0 }
0
0
{ ≥ 1 ... <8 }
0
50
Value
0.0
0.0
1.0
(0.0)
0.0
0.0
0 ms
20 ms
Value
Type
change
Init
Init
Init
Init
Init
Value
Type
change
Init
Init
Init
Init
5-77

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

D7-sys