Siemens SIMADYN D Manual page 128

System- and communication configuring
Hide thumbs Also See for SIMADYN D:
Table of Contents

Advertisement

STF variable name
System- and communication configuring D7-SYS - SIMADYN D
Edition 12.2003
• Channel name
− max. 8 characters
− ASCII characters with the exception of "Point" and @
− the channel name on a data interface must be unique.
− the channel name does not have a specific significance for
SINEC H1 layer 7.
• If address stage 1 and address stage 2 are not specified, then
SIMADYN D is a server as far as the associated STF utility is
concerned and defines a local variable. The channel name is part of
the associated variable name.
• Enter "." after the channel name
• Address stage 1
− can only be used in conjunction with address stage 2.
− max. 14 characters.
− if address stage 1 and 2 are used, SIMADYN D is a client as far as
the associated STF utility is concerned.
− address stage 1 is interpreted as symbolic name of the application
association, via which the STF utility is handled. Application
associations are configured with SINEC NML; they define the
communication paths between the applications. The application
association name is the only assignment between the SIMADYN D
software and the NML software.
• Address stage 2
− max. 20 characters.
− address stage 2 is the remote variable name for the
communications partner (server).
If SIMADYN D is a server regarding an STF utility, then SIMADYN D
defines a variable. The variable name has the following structure:
"Channelnamesubracknamepd"
• Channel name
Channel name as configured at AT, AR, US (refer to the Chapter
Connections of the communication blocks). It is precisely 8 characters
long. If the configured channel name is shorter, then it is made up to 8
characters using "_".
• Subrack name
Name of the subrack in which the SIMADYN D utility is configured. It
is precisely 6 characters long. If the configured name is shorter, then it
is made up to 6 characters using "_".
Communications configuring