Commissioning
Table 36: Channel settings Menu Item
Option
Show overrange of
user range values.
Show underrange of
user range values.
Specifying Limiting Values
Upper limit
Lower limit
Offset for Measurement Monitoring
Offset for diagnosis
measurement
overrange
Offset for diagnosis
measurement
underrange
*)
Factory setting
7.1.1.4.3

„Scaling" Menu Item

Save settings!
Click the [Write] or [Write all] button to write any settings you have made to the
I/O module.
Manual
Version 1.1.2
Description
*)
The "User limiting value overrange" diagnostic
function is activated and is displayed in the status
byte.
The "User limiting value overrange" diagnostic
function is deactivated and is not displayed in the
status byte.
*)
The "User limiting value underrange" diagnostic
function is activated and is displayed in the status
byte.
The "User limiting value underrange" diagnostic
function is deactivated and is not displayed in the
status byte.
Enter the upper limiting value of your required value range.
The value entered must fall within the value range
−32768 ... +32767.
Enter the lower limiting value of your required value range.
The value entered must fall within the value range
−32768 ... +32767.
Enter the offset value at which the "Measurement Range
Overrange" diagnostic message should be triggered.
Note: When selecting the sensor type 3.6-21mA (NAMUR
NE43), you are not permitted to determine this value.
Enter the offset value at which the "Measurement Range
Underrange" diagnostic message should be triggered.
Note: When selecting the sensor type 3.6-21mA (NAMUR
NE43), you are not permitted to determine this value.