F0 Protection - Canworld CDE360 Series Manual

Vector control ac drive
Table of Contents

Advertisement

CDE360 Vector Control AC Drive

F0 Protection

Function
Name
Code
F0.00
Under voltage threshold
F0.01
Over voltage threshold
F0.02
Input phase loss protection
F0.03
Output phase loss protection
F0.04
Short-circuit to ground upon
power-on
F0.05
AC drive over load protection gain
F0.06
Motor overload protection
F0.07
Motor overload protection gain
F0.08
Motor overload warning coefficient
F0.09
Under load protection
F0.10
Detection level of Under load
F0.11
Detection time of Under load
F0.12
Motor temperature sensor type
F0.13
Motor overheat protection threshold
F0.14
Motor overheat warning threshold
F0.15
Over-speed detection value
F0.16
Over-speed detection time
F0.17
Detection value of too large speed
deviation
F0.18
Detection time of too large speed
deviation
F0.19
Fault protection action selection 1
Unit's digit: input phase loss
0: Coasting stop
Ten's digit: output phase loss(same as unit's digit)
Hundred's digit: AC drive overload(same as unit's digit)
Thousand's digit: Motor overload(same as unit's digit)
Range
Module
dependent
Module
dependent
0~1
0~1
0~1
0.30~3.00
0~1
0.20~10.00
50~100
0~1
0.0~100.0
0.0~60.0
0~2
0.0~200.0
0.0~200.0
0.0~50.0
0.0~60.0
0.0~50.0
0.0~60.0
0000~2222
1: stop by stop mode
78
-
-
Chapter 5 Parameter List Table
Default
Step
0.1V
Module
dependent
0.1V
Module
dependent
1
1
1
1
0
1
1.00
0.01
1
1
1.00
0.01
80
1%
0
1
40.0
0.1%
1.0
0.1Sec
0
1
120.0
0.1℃
100.0
0.1℃
20.0
0.1%
5.0
0.1Sec
20.0
0.1%
1.0
0.1Sec
0000
1
2: continue running
Description
0: Disabled
1: Enabled
0: Disabled
1: Enabled
0: Disabled
1: Enabled
0: Disabled
1: Enabled
0: Disabled
1: Enabled
0: No sensor
1: PT100
2: PT1000

Advertisement

Table of Contents
loading

Table of Contents