CDE360 Vector Control AC Drive
Group d1: Motor Parameters
①
d1.01
motor stator
resistance
①
d1.02
motor rotor
resistance
①
d1.03
motor leakage
inductance
①
d1.04
motor mutual
inductance
①
d1.05
motor no-load
current
①
d1.06
Motor weaken
flux coefficient 1
①
d1.07
Motor weaken
flux coefficient 2
①
d1.08
Motor weaken
flux coefficient 3
Range:
0.001 ~ 65.535(drive power<=55kW)
0.0001 ~ 6.5535(drive power >55kW)
Unit: Ω
asynchronous motor stator resistance.
Range:
0.001 ~ 65.535(drive power <=55kW)
0.0001 ~ 6.5535(drive power >55kW)
Unit: Ω
asynchronous motor rotor resistance..
Range:
0.01 ~ 655.35(drive power <=55kW)
0.001 ~ 65.535(drive power >55kW)
Unit: mH
asynchronous motor leakage inductance.
Range:
0.1 ~ 6553.5(drive power <=55kW)
0.01 ~ 655.35(drive power >55kW)
Unit: mH
asynchronous motor mutual inductance
Range: 0.01 ~ motor rated current
(b0.08)(drive power <=55kW)
0.1 ~ b0.08(drive power >55kW)
Unit: A
asynchronous motor no-load current.
Range: 0.000 ~ 1.000
The flux coefficient corresponds to 20% of flux current.
Range: 0.000 ~ 1.000
The flux coefficient corresponds to 50% of flux current.
Range: 0.000 ~ 1.000
The flux coefficient corresponds to 80% of flux current.
Chapter 6 Parameters Description
Default: Model dependent
Default: Model dependent
Default: Model dependent
Default: Model dependent
Default: Model dependent
Default: 0.400
Default: 0.700
Default: 1.000