Group L0: Communication Setting - Canworld CDE360 Series Manual

Vector control ac drive
Table of Contents

Advertisement

CDE360 Vector Control AC Drive

Group L0: Communication Setting

L0.00
Baud rate
L0.01
Data format
L0.02
Slave address
L0.03
Response delay
L0.04
Communication
timeout detection
Range: 0~4
Set the baud rate for RS485 communication.
0: 4800 bits/s
1: 9600 bits/s
2: 19200 bits/s
3: 38400 bits/s
4: 57600 bits/s
Range: 0~3
Set the data format for RS485 communication.
0: 8 data bit, no check, 1 stop bit<8,N,1>
1: 8 data bit, no check, 2 stop bit <8,N,2>
2: 8 data bit, even parity check, 1 stop bit<8,E,1>
3: 8 data bit, odd parity check, 1 stop bit <8,O,1>
Range: 1~247
Set the drive communication address.
The slave address of zero is broadcast address, the address of 1~247 are
usable.
Range: 0~20
Unit: mSec
The interval from receiving data to replying data to the master.
Range: 0.0~60.0
Unit: Sec
Set L0.04 to zero, the communication timeout function is invalid.
Set L0.04 to non-zero, if the interval time between twice communication
exceed L0.04, the AC drive will display "Er31"(RS485 communication
fault)
Chapter 6 Parameters Description
Default: 1
Default: 1
Default: 1
Default: 2
Default: 0.0