Group E5: PID

E5.00
PID engineering
unit
E5.01
PID engineering
unit resolution
The PID engineering unit is convenient for customer using.Different engineering unit will be
converted to percentage in the AC drive PID regulator.The percentage value of final PID setting and
feedback will be again converted to the real value with engineering unit,and then shown to
customers.
Range: 0~1
This parameter determines the unit of PID regulator.
0: Percentage(%)
The following parameters' unit is determined by E5.00.
 E5.05(PID digital setting)
 E5.03(Minimum setting of PID
engineering unit)
 E5.02(Maximum setting of PID
engineering unit)
 E5.16(PID parameter
switchover deviation 1)
 E5.17(PID parameter
switchover deviation 2)
 E5.26(PID deviation limit)
Note:The above 12 parameters' unit will change immediately according to
E5.00.
Range: 0~3
0: No decimal
1: One decimal
This parameter determined the resolution of the following parameter:
 E5.05(PID digital setting)
 E5.03(Minimum setting of PID
engineering unit)
 E5.02(Maximum setting of PID
engineering unit)
 E5.16(PID parameter
Switchover deviation 1)
 E5.17(PID parameter
switchover deviation 2)
 E5.26(PID deviation limit)
Note:The resolution of above 12 parameters will change immediately
according to E5.01.
1: Pressure(MPa)
 E5.33(Upper limit of PID
feedback detection)
 E5.34(Lower limit of PID
feedback detection)
 E5.36(Wake up level)
 E5.39(Sleep level)
 A0.20(PID reference)
 A0.21(PID feedback)
2: Two decimal
 E5.33(Upper limit of PID
 E5.34(Lower limit of PID
 E5.36(Wake up level)
 E5.39(Sleep level)
 A0.20(PID reference)
 A0.21(PID feedback)
Chapter 6 Parameters Description
Default: 0
Default: 1
3: Three decimal
feedback detection)
feedback detection)