Group H1: Ai/Ao Calibration - Canworld CDE360 Series Manual

Vector control ac drive
Table of Contents

Advertisement

CDE360 Vector Control AC Drive
H0.25
Product series
number lower
bits
H0.26
OTP version

Group H1: AI/AO Calibration

These parameters of H1.00~H1.11 are used to calibrate analog inputs, they have been calibrated
upon delivery. Generally, you need not perform calibration in the common applications.
The actual voltage indicates the actual input voltage value measured by instruments such as the
multi-meter.
The display voltage is the drive calculated value which can be monitored from A0.11~A0.13.
During calibration, send two voltage values to each AI terminal, and save the measured values and
displayed values to the function codes H1.00~H1.11, then the AC drive will automatically perform AI
zero offset and gain calibration.
 H1.00~H1.03 are used to calibrate AI1.
 H1.04~H1.07 are used to calibrate AI2.
 H1.08~H1.11 are used to calibrate AI3.
 When drive restore factory default value, H1.00~H1.11 will be resumed to factory
calibrated value.
H1.00
AI1 actual
voltage 1
H1.01
AI1 display
voltage 1
H1.02
AI1 actual
voltage 2
H1.03
AI1 display
voltage 2
Function Code
H1.04
Range: 0~65535
Read only.
Range: 0.00~99.99
Read only.
Range: 0.500~4.000
Unit: V
It is used to input the AI1 measured voltage.
Range: 0.500~4.000
Unit: V
It is used to input the AI1 display voltage(A0.11).
Range: 6.000~9.999
Unit: V
It is used to input the AI2 measured voltage.
Range: 6.000~9.999
Unit: V
It is used to input the AI1 display voltage(A0.12).
The parameters used to calibrate AI2 and AI3 as below:
Name
AI2 actual voltage 1
Chapter 6 Parameters Description
Default: Factory setting
Default: Factory setting
Default: Factory setting
Default: Factory setting
Default: Factory setting
Default: Factory setting
Function Code
H1.08
AI3 actual voltage 1
Name