15.4 Replacing Firmware (DKC**.3-016-7-FW)

Replacing or Exchanging Drive Components
Secure parameters (DriveTop)
Set Parameter
P-0-4021, Baud-Rate RS-232/485
9600)
Close DriveTop
Start DOLFI
Press Button "Connect"
Open IBF- le of the mware by pressing button "Open le"
Transfer the three les of the IBF- le by pressing button "Transfer le"
and con rm the transfers.
In event of download problems you have to reduce the Baud rate (see
menu item "Settings"; see also help system of DOLFI)
Restart the drive with "Serial disconnecting"
Load parameters (DriveTop)
customerservice@hyperdynesystems.com
15-9
to 0 (Baud rate
|