Rexroth Indramat ECODRIVE03 Series Project Planning Manual page 144

Drive controllers
Table of Contents

Advertisement

4-112
ECODRIVE03 DKC**.040, DKC**.100, DKC**.200
customerservice@hyperdynesystems.com
To prepare a bus cable, proceed as follows:
Use cable DIN EN50170 / 2 edition 1996
Strip cable (see previous illustration)
Insert both cores into screw terminal block
Note:
Do not switch A and B.
Press cable sheath between both clamps
Screw both strands into screw terminals
A
B
A
B
A B
A B
1
Switch connection for the rst and nal slave in the Pro bus-DP
2
The cable shield must be placed bare on the metal guide
Fig. 4-189: Bus links for the rst and last slave, bus connector with 9-pin D-SUB
socket, INS 0541
A
B
A
B
A B
A B
1
Terminating resistor is o
2
The cable shield must be placed bare on the metal guide
Fig. 4-190: Bus link for all other slaves, bus connector with 9-pin D-SUB socket,
INS 0541
|