User response: Complete the following steps:
1. Check the CMM or FSM event log for any fan or cooling related issues.
2. Make sure that the airflow at the front and rear of the chassis is not obstructed and that fillers are in place and
correctly installed.
3. Make sure that the room temperature is within operating specifications.
4. Make sure that the DIMM baffles are in place.
5. If the problem persists and there are no other DIMMs with the same indication, replace the DIMM.
806f090c-2011ffff
[PhysicalMemoryElementName] on Subsystem [MemoryElementName] Throttled.
Explanation: This message is for the use case when an implementation has detected Memory has been Throttled.
May also be shown as 806f090c2011ffff or 0x806f090c2011ffff
Severity: Warning
Alert Category: System - Other
Serviceable: Yes
CIM Information: Prefix: PLAT and ID: 0142
SNMP Trap ID: 22
Automatically notify Support: No
User response: Complete the following steps:
1. Check the CMM or FSM event log for any fan or cooling related issues.
2. Make sure that the airflow at the front and rear of the chassis is not obstructed and that fillers are in place and
correctly installed.
3. Make sure that the room temperature is within operating specifications.
4. Make sure that the DIMM baffles are in place.
5. If the problem persists and there are no other DIMMs with the same indication, replace the DIMM.
806f090c-2012ffff
[PhysicalMemoryElementName] on Subsystem [MemoryElementName] Throttled.
Explanation: This message is for the use case when an implementation has detected Memory has been Throttled.
May also be shown as 806f090c2012ffff or 0x806f090c2012ffff
Severity: Warning
Alert Category: System - Other
Serviceable: Yes
CIM Information: Prefix: PLAT and ID: 0142
SNMP Trap ID: 22
Automatically notify Support: No
User response: Complete the following steps:
1. Check the CMM or FSM event log for any fan or cooling related issues.
2. Make sure that the airflow at the front and rear of the chassis is not obstructed and that fillers are in place and
correctly installed.
3. Make sure that the room temperature is within operating specifications.
4. Make sure that the DIMM baffles are in place.
5. If the problem persists and there are no other DIMMs with the same indication, replace the DIMM.
806f090c-2011ffff • 806f090c-2012ffff
Chapter 6. Troubleshooting
253