80070101-3701ffff • 80070101-3702ffff
CIM Information: Prefix: PLAT and ID: 0520
SNMP Trap ID: 12
Automatically notify Support: No
User response: Complete the following steps until the problem is solved:
1. Check the Chassis Management Module or Flex System Manager event log for any fan- or cooling-related issues.
2. Make sure that the airflow at the front and rear of the chassis is not obstructed and that fillers are in place and
correctly installed.
3. Make sure that the room temperature is within operating specifications.
80070101-3701ffff
Sensor Inlet 1 Overtemp has transitioned from normal to non-critical state.
Explanation: The inlet 1 temperature has exceeded its specified threshold. The compute node has attempted a soft
shutdown.
May also be shown as 800701013701ffff or 0x800701013701ffff
Severity: Warning
Alert Category: Warning - Temperature
Serviceable: Yes
CIM Information: Prefix: PLAT and ID: 0520
SNMP Trap ID: 12
Automatically notify Support: No
User response: Complete the following steps until the problem is solved:
1. Check the Chassis Management Module or Flex System Manager event log for any fan- or cooling-related issues.
2. Make sure that the airflow at the front and rear of the chassis is not obstructed and that fillers are in place and
correctly installed.
3. Make sure that the room temperature is within operating specifications.
80070101-3702ffff
Sensor Inlet 2 Overtemp has transitioned from normal to non-critical state.
Explanation: The inlet 2 temperature has exceeded its specified threshold. The compute node has attempted a soft
shutdown.
May also be shown as 800701013702ffff or 0x800701013702ffff
Severity: Warning
Alert Category: Warning - Temperature
Serviceable: Yes
CIM Information: Prefix: PLAT and ID: 0520
SNMP Trap ID: 12
Automatically notify Support: No
User response: Complete the following steps until the problem is solved:
1. Check the Chassis Management Module or Flex System Manager event log for any fan- or cooling-related issues.
2. Make sure that the airflow at the front and rear of the chassis is not obstructed and that fillers are in place and
correctly installed.
3. Make sure that the room temperature is within operating specifications.