80070101-0301ffff
Sensor CPU 1 Overtemp has transitioned from normal to non-critical state.
Explanation: The microprocessor 1 temperature has risen above its specified threshold.
May also be shown as 800701010301ffff or 0x800701010301ffff
Severity: Warning
Alert Category: Warning - Temperature
Serviceable: Yes
CIM Information: Prefix: PLAT and ID: 0520
SNMP Trap ID: 12
Automatically notify Support: No
User response: Complete the following steps until the problem is solved:
1. Check the Chassis Management Module or Flex System Manager event log for any fan- or cooling-related issues.
2. Make sure that the airflow at the front and rear of the chassis is not obstructed and that fillers are in place and
correctly installed.
3. Make sure that the room temperature is within operating specifications.
80070101-0302ffff
Sensor CPU 2 Overtemp has transitioned from normal to non-critical state.
Explanation: The temperature of microprocessor 2 has exceeded its specified threshold.
May also be shown as 800701010302ffff or 0x800701010302ffff
Severity: Warning
Alert Category: Warning - Temperature
Serviceable: Yes
CIM Information: Prefix: PLAT and ID: 0520
SNMP Trap ID: 12
Automatically notify Support: No
User response: Complete the following steps until the problem is solved:
1. Check the Chassis Management Module or Flex System Manager event log for any fan- or cooling-related issues.
2. Make sure that the airflow at the front and rear of the chassis is not obstructed and that fillers are in place and
correctly installed.
3. Make sure that the room temperature is within operating specifications.
80070101-0303ffff
Sensor CPU 3 Overtemp transitioned from normal to non-critical state.
Explanation: The temperature of microprocessor 3 has exceeded its specified threshold.
May also be shown as 800701010303ffff or 0x800701010303ffff
Severity: Warning
Alert Category: Warning - Temperature
Serviceable: Yes
CIM Information: Prefix: PLAT and ID: 0520
SNMP Trap ID: 12
Automatically notify Support: No
User response: Complete the following steps until the problem is solved:
1. Check the Chassis Management Module or Flex System Manager event log for any fan- or cooling-related issues.
2. Make sure that the airflow at the front and rear of the chassis is not obstructed and that fillers are in place and
correctly installed.
80070101-0301ffff • 80070101-0303ffff
Chapter 6. Troubleshooting
111