80070301-2c01ffff • 80070301-2c03ffff
3. Make sure that the room temperature is within operating specifications.
4. Make sure that the microprocessor 4 heat sink is securely installed.
5. Make sure that the microprocessor 4 heat sink is installed correctly and the thermal material is correctly applied.
6. Replace microprocessor 4.
80070301-2c01ffff
Sensor Mezz Exp 1 temp has transitioned to non-recoverable from a less severe state.
Explanation: The temperature of the I/O expansion adapter in I/O expansion connector 1 has exceeded its specified
threshold. The compute node has attempted a soft shutdown.
May also be shown as 800703012c01ffff or 0x800703012c01ffff
Severity: Error
Alert Category: Critical - Temperature
Serviceable: Yes
CIM Information: Prefix: PLAT and ID: 0524
SNMP Trap ID: 0
Automatically notify Support: No
User response: Complete the following steps until the problem is solved:
1. Check the Chassis Management Module or Flex System Manager event log for any fan- or cooling-related issues.
2. Make sure that the airflow at the front and rear of the chassis is not obstructed and that fillers are in place and
correctly installed.
3. Make sure that the room temperature is within operating specifications.
4. If there are no other thermal issues, replace the I/O expansion adapter.
80070301-2c02ffff
Sensor Mezz Exp 2 temp has transitioned to non-recoverable from a less severe state.
Explanation: The temperature of the I/O expansion adapter in I/O expansion connector 2 has exceeded its specified
threshold. The compute node has attempted a soft shutdown.
May also be shown as 800703012c02ffff or 0x800703012c02ffff
Severity: Error
Alert Category: Critical - Temperature
Serviceable: Yes
CIM Information: Prefix: PLAT and ID: 0524
SNMP Trap ID: 0
Automatically notify Support: No
User response: Complete the following steps until the problem is solved:
1. Check the Chassis Management Module or Flex System Manager event log for any fan- or cooling-related issues.
2. Make sure that the airflow at the front and rear of the chassis is not obstructed and that fillers are in place and
correctly installed.
3. Make sure that the room temperature is within operating specifications.
4. If there are no other thermal issues, replace the I/O expansion adapter.
80070301-2c03ffff
Sensor Mezz Exp 3 temp has transitioned to non-recoverable from a less severe state.
Explanation: The temperature of the I/O expansion adapter in I/O expansion connector 3 has exceeded its specified
threshold. The compute node has attempted a soft shutdown.
May also be shown as 800703012c03ffff or 0x800703012c03ffff
Severity: Error
120
IBM Flex System x440 Compute Node Types 7917 and 2584: Installation and Service Guide