Connection With Intelligent I/O Units - Toshiba V Series User Manual

Integrated controller
Hide thumbs Also See for V Series:
Table of Contents

Advertisement

Chapter 1 Overview
1.3

Connection with Intelligent I/O Units

1
Intelligent I/O units can be connected by way of IOBUS. Table 1-2 shows a list of I/O units and
Table 1-3 shows accessory units.
To connect an intelligent I/O, an IOBUS terminal (UT5U11) is used.
For how to register system components using the Engineering Tool 2, see Chapter 3,
"Software Function."
Name
Analog input
universal
Analog input
1 to 5V
Analog input
1 to 5V
Thermocoupl
e input
Resistance
Temperature
Detector
Analog output AO01 8
Analog output AO02 4
Digital input
Digital output
Pulse input
Pulse output
Loop I/O
(Current
output type)
Loop I/O
(Pulse output
type)
Note 1
Up to 16 I/O modules can be connected to one I/O bus.
4
Table 1-2 List of I/O units
Number of
Model
channels
AI01
8
One of 1 to 5V (4 to 20mA)
/mV/V/TC
AI02
4
Input: 1 to 5 V
AI03
4
Input: 1 to 5 V, with a distributor
circuit
TC01 8
Input: K, J, T, E, B, R, S
RT01 4
Input: RTD Pt100, JPt100
Output: 4 to 20 mA
Output: 4 to 20 mA
DI01
32
Input: No-voltage contact
(A 24V power supply from an
external source is required for an
input circuit.)
DO01 32
Output: FET open drain
(A 24V power supply from an
external source is required for an
output circuit.)
PI01
4
Input: No-voltage, voltage
PO01 4
Output: No-voltage, voltage
LP03
1 loop
Input:
AI: 1 to 5 V 4 channels
DI: No-voltage contact 3
channels
Output:
MV: 4 to 20 mA 1 channel
AO: 1 to 5 V 2 channels
DO: FET open drain 3 channels
LP04
1 loop
Input:
AI: 1 to 5 V 4 channels
DI: No-voltage contact 3
channels
Output:
MV: Pulse width 1 channel
AO: 1 to 5 V 2 channels
DO: FET open drain 3 channels
Insulation
Input/output
between channels
Not provided
Provided
Provided
Provided
Provided
Not provided
Provided
Not provided
Not provided
Not provided
Not provided
Insulated between
AI/O and DI/O,
and between AI/O
and power supply.
Insulated between
AI/O and DI/O,
and between AI/O
and power supply.
Model 1000 Loop Controller L1 LC511, 512 User's Manual
IO bus
Remarks
rate
19.2kbps
19.2kbps
19.2kbps
19.2kbps
19.2kbps
19.2kbps
19.2kbps
19.2kbps
19.2kbps
19.2kbps
19.2kbps
19.2kbps
19.2kbps

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

L1 1000L1 lc511L1 lc512

Table of Contents