Conventional single-loop controllers (TOSDIC 212D/215D)
Classification
Abbrev
Linearization
LOG
Natural logarithm
Linearization
EXP
Exponent
Counter/timer
SUM
Integration
Counter/timer
TM1
Timer 1
Counter/timer
TM2
Timer 2
Counter/timer
DEL
On/Off delay timer
Counter/timer
CHD
Status change
detection
Counter/timer
RSM
Integration with
reset value
Selector/limiter
MAX
Maximum value
Selector/limiter
MIN
Minimum value
Selector/limiter
AVE
Average value
Selector/limiter
MED
Median value
Selector/limiter
LMT
Limiter
Compare
: Equivalent instruction is provided;
Name
Specification
Y=H1*ln (U1) + H2
Y=H1*exp (U1) + H2
If U2 ≠ 0 then Y=H1 + (H2*U1 + H3)
else Y=Y
+ (H2*U1 + H3)
− 1
If U2 ≠ 0 then Y=H1*U1 + H2
else Y=Y
− CTS if Y < 0 then Y=0
− 1
If previous output value > 0 then Y=Y
if Y < 0 then Y=0
if Y
≤ 0, U2 ≠ 0 then Y=H1*U1 + H2
− 1
≤ 0, U2=0 then Y=0
if Y
− 1
Y turns ON in H1 seconds after U1 turns ON and Y
turns OFF in H2 seconds after U1 turns OFF.
Y turns ON for one cycle when a change in U1 − U6
is detected.
if U2 ≠ 0 then Y=U1*CTS / K + H1
else if Y < H3 then Y=U1*CTS/K + Y − 1
else Y=U1*CTS/K + Y − 1 − H3
Y = max (U1, U2, U3, U4, U5, U6)
Y = min (U1, U2, U3, U4, U5, U6)
Y = (U1 + U2 + U3 + U4 + U5 + U6) / n (n=2~6)
Y = { Median value of U1, U2, U3, U4, U5 and U6}
H1*U2+H2 ≤ U1 ≤ H3*U2+H4 Y=U1
H1*U2 + H2 > U1 Y= H1*U2+H2
H3*U2 + H4 < U1 Y= H3*U2+H4
: Specification partly differs;
Comparison
When H1=1.0 and H2=0.0, LN is an equivalent instruction
(however, Y=0 when U1=0) and (LOG) is a substitute
application.
When H1=1.0 and H2=0.0, EXP is an equivalent
instruction and (EXP) is a substitute application.
When PV tag is registered, this function is executed by
standard input processing (integration value). For other
than above, (SUM) is a substitute application.
Data type of TOFU1 is converted to REAL_TO_TIME and
data is corrected by H2 and H3 and then enter data.
− CTS
Data type of TPU1 is converted to REAL_TO_TIME and
− 1
data is corrected by H2 and H3 and then enter data.
DEL_L
Substitute application (CHD)
RSM_L
MAX_REAL
MIN_REAL
AVE_REAL
Substitute application (MED)
When H1=H3=0 or H2=H4=0 and U1=1, LIMIT_REAL is
an equivalent instruction.
Including above, (LMT) is a substitute application,
checked by high limit and then low limit.
:Equivalent instruction is not provided
LC512/,511
Equivalent instructions and precautions