A.4.12 Loop I/O Module (LP03)
• Specifications
Analog input signal (AI):
Analog output signal (AO):
Manipulated variable signal (MV):
Digital input signal (DI):
Digital output signal (DO):
Communication method (IOBUS):
Supply power:
Consumption current:
Method to remove/install the main
unit:
Operating environment:
Installation:
Mass:
Adaptable terminal block:
6F8C1135
1−5VDC, 4 points
1−5 DC, 2 points
4−20mA, 1 point
Dry contact, 3 points
Dry contact, 3 points
RS-485, semi-duplex, asynchronous,
multi-drop 19.2Kbps
24VDC, +10%, −15%
Main unit:
Approx. 150mA
DI/DO section: Approx. 40mA
Main unit can be removed or installed online (while
power is applied)
Temperature: 0 to 55°C
Humidity: 10 to 90%RH (no condensation)
35 mm width DIN rail installation
(DIN rail depth 15mm or more)
Main unit
Approx. 220g,
Terminal block section Approx. 220g
UT5P11 (Width dimension: 60 mm)
A.4 Intelligent I/O Specifications