Appendix E Details of Variables
(5) System signal output (write)
ZW
800
WDT signal output
801
LDU ALM_LED lights
(6) System signal output (readout / write) (Note 1)
ZW
802
LDU display loop (Stn1)
to
809
LDU display loop (Stn8)
The upper 1-byte is the loop number currently displayed and the lower 1-byte is a command to change the loop
number. The display loop of LD512H can be changed by writing a command (1 to 8) in this area (1W). When you
write a value of 1 to 8, it is not necessary to mask the upper byte. In addition, a command to change the loop
number to LD512H is made only once when the value of the loop number command changes. It is not necessary to
change the value back to "0".
Note 1: This item is valid for LC511,512 System Program V2.20 or later and only when used in the LC511,512 and
LD512H firmware V2.2 or later.
E
154
Use
F
E
0: Normal (External signal: ON)
1: WDT output (External signal: OFF) (External signal is OFF while
continuous output ZW800 is "1")
<0> Condition when LDU1 ALM_LED lights (0: Unlit (Auto system / 1:
Lights)
<7> Condition when LDU8 ALM_LED lights (0: Unlit (Auto system / 1:
Lights)
Use
F
E
Loop number display (*1) (0:
Without corresponding station / 1 to
8: Display loop)
Loop number display (0: Without
corresponding station / 1 to 8:
Display loop)
D
C
B
A
9
8
7
7
to
D
C
B
A
9
8
7
Loop number command (0: Without
request / 1 to 8: Loop command
to
Loop number command (0: Without
request / 1 to 8: Loop command
Model 1000 Loop Controller L1 LC511,512 User's Manual
6
5
4
3
2
1
0
6
5
4
3
2
1
0
6
5
4
3
2
1
0