Analog Output Module (Ao02) - Toshiba V Series User Manual

Integrated controller
Hide thumbs Also See for V Series:
Table of Contents

Advertisement

Appendix A LC51* and Expansion Module
A.4.7

Analog Output Module (AO02)

• Specifications
Output signal and number of points:
Isolation between channels:
Load resistance:
Communication method (IOBUS):
Supply power:
Consumption current:
Method to remove/install the main
unit:
Operating environment:
Installation:
Mass:
Adaptable terminal block:
• Connection
The terminal block module to be used is UT5O11.
A
120
Current output 4−20mA, 4 points
Provided (Insulated)
0−750Ω
RS-485, semi-duplex, asynchronous,
multi-drop 19.2Kbps
24VDC, +10%, −15%
Approx. 200mA
Main unit can be removed or installed online (while
power is applied)
Temperature: 0 to 55°C
Humidity: 10 to 90%RH (no condensation)
35 mm width DIN rail installation
(DIN rail depth 15mm or more)
Main unit Approx. 200g
UT5O11 (Width dimension: 40 mm)
Terminal block TB1
AO1
( )
AO1
AO1
( )
AO2
( )
AO2
AO2
( )
Terminal block TB2
AO3
( )
AO3
AO3
( )
AO4
( )
AO4
AO4
( )
Model 1000 Loop Controller L1 LC511, 512 User's Manual