Toshiba V Series User Manual page 167

Integrated controller
Hide thumbs Also See for V Series:
Table of Contents

Advertisement

Event
Trace Contents
Level
No.
C108 Flash ROM BCC check
Major
Periodic diagnosis Error
error
failure
C110 Memory R/W check
Major
Initial diagnosis
error
failure
C111 Memory R/W check
Major
Periodic diagnosis Error
error
failure
C113 Memory erased
Major
Initial diagnosis
failure
C119 User information DL
Major
Initial diagnosis
error
failure
C300 Intelligent I/O start error
Major
Initial diagnosis
failure
C310 All intelligent I/O
Major
Periodic diagnosis Error
stations rundown
failure
D100 User task stop illegal
Major
In executing user
instruction detected
failure
task
D102 User task stop boundary
Major
In executing user
over
failure
task
Table D-1 Error Trace (4 / 5)
Timing
Exec
Remarks
Error was detected in
rundown
flash ROM BCC
calculation.
Error
Error was detected in
rundown
memory write/read
compare check.
Error was detected in
rundown
memory write/read
compare check.
Error
Loss of memory data in
rundown
user data area was
detected.
Error
An error detected in
rundown
downloading user
information from FROM to
SRAM
Error
An error detected in
rundown
initializing intelligent I/O
All the intelligent I/O
rundown
stations unable to
communicate
Error
An instruction undefined
rundown
in user program was
detected.
Error
User task is over specified
rundown
size.
Task
Address
Aux1
Aux2
BCC
Block No.
Number of
error
occurrences
Error
address
IP
IP
IR
(absolute)
(relative)
IP
IP
IR
(absolute)
(relative)
Aux3
Cause
Maintenance
Flash memory failure
Replace the CPU module
and restart the system.
Or, contact TOSHIBA
service station.
RAM memory defective
Replace the CPU module
and restart the system.
Or, contact TOSHIBA
service station.
RAM memory defective
Replace the CPU module
and restart the system.
Or, contact TOSHIBA
service station.
The system was left for
Load the program from
a long time with no
the Tool, and restart the
battery mounted. Or, the
system. If the error is not
RAM memory is
remedied after loading the
defective.
program, replace the CPU
module and restart the
system. Or, contact
TOSHIBA service station.
RAM memory faulty
Load the program from
Tool, and restart the
system. In case of no
recovery after program
loading, replace the CPU
module, and restart the
system. Or, contact
TOSHIBA service station.
S20L board error
Transmission error
Check the I/O bus
occurred on all the I/O
connections.
buses
1. Instruction not
1. Check the tables in the
supported
Instruction Manual for
2. Memory error
the range of instructions
supported.
2. Clear the memory of
the controller itself, and
download the program
again.
Memory failure
Clear the memory of the
controller its elf, and
download the program
again.

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

L1 1000L1 lc511L1 lc512