Appendix E Details of Variables
Item name
Signal type
code
E
156
Abbr.
SIG
[Input signal type]
Unused
Standard processing for this instrument will not be
performed.
No actual input
Since the conversion processing for input counter is
not performed, a calculated value is substituted to
PV value by program and this is used as an internal
instrument.
4 − 20mA 2-wire
Actual input signal. 4 − 20mA of 2-wire transmitter is
method
selected.
4 − 20mA 4-wire
Actual input signal. 4 − 20mA of 4-wire transmitter is
method
selected.
1 − 5V
Actual input signal. 1 − 5V from a converter, etc. is
selected.
Pt100 new
Actual input signal. RTD (new JIS, Pt100) is
selected.
Pt100 old
Actual input signal. RTD (old JIS, Pt100) is selected.
K-THC
Actual input signal. Type K thermocouple is
selected.
T-THC
Actual input signal. Type T thermocouple is
selected.
J-THC
Actual input signal. Type J thermocouple is
selected.
E-THC
Actual input signal. Type E thermocouple is
selected.
B-THC
Actual input signal. Type B thermocouple is
selected.
R-THC
Actual input signal. Type R thermocouple is
selected.
S-THC
Actual input signal. Type S thermocouple is
selected.
Pulse contact
Actual input signal. Pulse contact input is selected.
Pulse voltage
Actual input signal. Pulse voltage input is selected.
mV
Actual input signal. mV voltage input is selected.
Note: Processing items differ depending on the signal type.
When SIG is "4 − 20mA 2-wire method" to "S-THC" and mV
The standard processing for analog input is executed. The same
processing is executed except for sensor error (PVI) occurrence
condition.
• In the case other than mV
AI input < 4480 or AI input = 32767
• In the case of mV
Larger than input count high limit (CH) or smaller than input count
low limit (CL) [Considering the deviation of AI, PVI is detected
when the input is shifted upward or downward a little from CH or
CL.]
When SIG is "Pulse contact" or "Pulse voltage," the standard
processing for pulse input is executed.
Description
[Description]
Model 1000 Loop Controller L1 LC511,512 User's Manual
Data type
DSP
[unit]
UINT