No.
D104 User task stop POU No.
Major
In executing user
undefined
failure
task
D106 User task stop operation
Major
In executing user
stack error
failure
task
D107 User task stop I/O direct
Major
In executing user
input/output error
failure
task
D108 Task stall
Major
Periodic diagnosis Error
failure
D300 Total control stop
Major
Periodic diagnosis Error
failure
Table D-1 Error Trace (5 / 5)
Timing
Exec
Remarks
Error
Specified function block or
rundown
function cannot be found.
Error
Disagreement between
rundown
inputs to and outputs from
the stack.
Error
User task stop due to I/O
rundown
direct input/output error
Main scan is in congestion
rundown
or is stopped.
Total control is in
rundown
congestion.
Task
Address
Aux1
Aux2
IP
IP
IR
(absolute)
(relative)
IP
IP
IR
(absolute)
(relative)
IP
IP
IR
(absolute)
(relative)
Aux3
Cause
Maintenance
The specified function or
Set a function block or a
function block has not
function POU No. within
been downloaded. Or,
the normal range (2048 to
the POU No. is wrong.
4095) and, after compiling
it by the caller project,
download again.
Compile is not normal.
Compile normally, then
download again.
I/O card error
Replace the I/O card as
quickly as possible.
Possible cause is too
Set scan cycle again, or
short a set main scan
check and correct the
time compared with
program.
program execution time,
or an infinite loop
formed of part of the
program.
System program error
Reset the error and restart
the system. Collect the
system log and contact
TOSHIBA.