Item name
Abbr.
Simulation
SIMM
Indicator value PV of indicator registered by [Controller variable] is
method
used, loop-back simulation method of controllers is registered.
Simple loop-back
Program loop-back (For future use)
PV/PVC
DIC
This is used when PV value is corrected by application program.
direct
PV = PVC: PV is set by standard input processing.
PV<>PVC: As a result of standard input processing, PVC is corrected
by application program to set PV.
(Correction by application program can be used only for instantaneous
value (current/pulse). This cannot be used for integrated value.)
PV value
PVC
The result of standard input processing. This value is referenced when
before
PV is corrected by application program.
application
Caution: When you correct PV by application program, set PV
correction
6F8C1135
Description
[Simulation]
When the simulation flag (SIM) is ON, the output
of the controller is looped back to PV
automatically.
considering SCN. Otherwise, even if SCN = OFF is set, PV
cannot be changed manually.
E.2 Tag Variables (PL, LP, PB)
[Description]
Data type
DSP
[unit]
UINT
REAL
[EU]
E
161