Toshiba V Series User Manual page 133

Integrated controller
Hide thumbs Also See for V Series:
Table of Contents

Advertisement

• Check to make sure that wire connection to the power supply terminal block and
RS485 terminal block is correct.
• If power is applied with incorrect wire connection, burnout or electric shock may result.
• When you connect this device, provide 50 mm or more space above and below the
device.
Item
Operating ambient
temperature
Storage temperature
Relative humidity
Dust concentration
Corrosion resistance
Vibration resistance
Impact resistance
Altitude
RS-232C
RS-485
Target value setting
(SV)
Manual operation
(MV)
Indicators
PV bar graph
SV bar graph
MV bar graph
Control mode
indication
Digital indication
Error indications
6F8C1135
Caution
Table A-8 LD512H Hardware Specifications (1)
0 to 55 ° C
− 25 to 70 ° C
5% to 95% (with no condensation)
3
0.3 mg/m
or less
No corrosive gas shall be present.
3G or less (5 to 33Hz, 15 minutes), X, Y and Z
40G or less
2000 m or lower
Cable length: 15 m or shorter, modular jack connector
Cable length: 200 m or shorter, M3.5 screw terminal
connection
UP/DOWN switches on the front panel
Changing speed NORMAL: About 100 seconds/full scale
FAST: About 10 seconds/full scale
OPEN/CLOSE/FAST switch system
Two response speeds selectable
NORMAL: About 40 seconds/full scale
FAST: About 5 seconds/full scale
Scale length (90 mm), Resolution (1%), Red
Scale length (90 mm), Resolution (1%), Green
Scale length (45 mm), Resolution (2%), Red
Manual (M): Red LED
Auto (A): Yellow LED
Remote setting: Yellow LED
PV, SV or MV value is displayed by 5-digit, 7-segment
LED.
Process alarm (ALM), Red LED
HALT alarm (HLT), Red LED
Computer/Local (CMP), Yellow LED
Remote/Manual (R/M), Green LED
A.3 LD512H Specifications
Specifications
Remarks
A
111