(3) Select <Parameter Copy> from the <Edit> menu and copy the initial value set in the Tool.
When a dialog box appears, select "Initial value" for Copy contents and click
(4) Register necessary parameters.
Minimum required items for tag registration are shown below. Other items can be left as
initial values. Set any of these items if necessary. For details of all parameters, see E.3
"Tag Variables (PV, LP, PB)."
Record No.
(Array
notation)
Item
TAG (Tag No.)
SIG (Signal type)
CH
(Input count high limit)
CL
(Input count low limit)
IP
(Input hardware address)
SIMM
(Simulation method)
6F8C1135
Figure 4-7
Table 4-3 PV: Indicator
Record 1 (PV [0]) Record 2 (PV [1])
PV1
PV2
1 − 5V
1 − 5V
4000
4000
800
800
00 − 01 − 01 − 00 − 02
00 − 01 − 01 − 00 − 03
(SLP03 AI1)
(SLP03 AI1)
Standard
Standard
4.3 Tag Registration
.
Supplementary explanation
(Caution)
This name becomes the
variable name (tag variable).
Register 1 − 5V for analog input
(AI) of SLP03 (SLP04).
Since the input count value of
SLP03 is 12-bit resolution, 0%:
800 to 100%: 4000. In the case
of SAI01, its resolution is 15-bit
resolution (0%: 6400 to 100%:
32000). The initial value for tag
is 6400 to 32000.
LP03 AI point starts from 02.
(Point 1: 02 to Point 4: 05)
If I/O is not connected, PV input
must be simulated. If "Standard"
is selected to set in the
simulation mode, MV
automatically will be sent back
to PV.